Sweden Building 05K0121
Start Page
General Information
Year of construction | 1889 |
---|---|
Category | Office |
Boundaries | One building |
Ownership Category | Private company |
Total floor area (BRA), m2 | 2100.0 |
OID, m2 | 2150.0 |
Interior height, m | 3.0 |
Year of construction 1 (taxation year) | 1988 |
Year of construction 2 (Year of construction) | 1889 |
County | Västernorrland County, Sweden |
Mean annual temperature during the calculation period[1] | 4.13333333333 |
Mean annual temperature at the site | 3.6 |
Start of the period (first day of the month) | 2004/10/01 |
End of the period (last day of the month) | 2005/09/01 |
References | Swedish Energy Agency[2] |
Areas by category, m2 (Gross Floor Area)
- Offices | 2100.0
|
---|---|
Total | 2100.0 |
References | Swedish Energy Agency[2] |
Purchased energy for the period [MWh/year]
Electricity, total | 186.0 |
---|---|
District heating | 217.4 |
Oil-fired boiler | 0.0 |
Natural gas | 0.0 |
Town gas | 0.0 |
Digester / landfill gas | 0.0 |
Pellets | 0.0 |
Wood chips | 0.0 |
Logs | 0.0 |
District cooling | 0.0 |
Other | 0.0 |
Total | 403.4 |
References | Swedish Energy Agency[2] |
Purchased energy, normal year [MWh/year]
Electricity, total | 186.0 |
---|---|
District heating | 226.987443946 |
Oil-fired boiler | 0.0 |
Natural gas | 0.0 |
Town gas | 0.0 |
Digester / landfill gas | 0.0 |
Pellets | 0.0 |
Wood chips | 0.0 |
Logs | 0.0 |
District cooling | 0.0 |
Other | 0.0 |
Total | 412.987443946 |
References | Swedish Energy Agency[2] |
Purchased energy per area [kWh/m2]
Electricity, total | 88.5714285714 |
---|---|
Electric heating | 0.0 |
Other electricity | 88.5714285714 |
District heating | 108.089259022 |
Oil-fired boiler | 0.0 |
Natural gas | 0.0 |
Town gas | 0.0 |
Digester / landfill gas | 0.0 |
Pellets | 0.0 |
Wood chips | 0.0 |
Logs | 0.0 |
District cooling | 0.0 |
Other | 0.0 |
Total | 196.660687593 |
Breakdown of electricity use [kWh/m2]
Electric heating | 0.0 |
---|---|
Heat pumps | 0.0 |
Refrigeration | 3.19047619048 |
Heat pumps used for cooling | 0.0 |
Pumps | 2.58728571429 |
Fans | 9.8574829932 |
Lighting | 20.7800475059 |
PCs | 6.04166666667 |
Large computers / servers | 21.4285714286 |
Printers | 2.80342857143 |
Copiers | 4.04761904762 |
Air compressors | 0.0 |
Small kitchens / coffee rooms | 5.1619047619 |
Large kitchens | 0.0 |
Elevators | 0.47619047619 |
Laundry | 0.0 |
Electric engine heaters | 0.0 |
Circulation fans | 0.0 |
Miscellaneous | 12.1472789116 |
Total | 88.5219522678 |
References | Swedish Energy Agency[2] |
Breakdown of electricity use [%]
Electric heating | 0.0 |
---|---|
Heat pumps | 0.0 |
Refrigeration | 3.60416383591 |
Heat pumps used for cooling | 0.0 |
Pumps | 2.92276169696 |
Fans | 11.1356366875 |
Lighting | 23.4744568704 |
PCs | 6.82504905494 |
Large computers / servers | 24.2070705397 |
Printers | 3.16693034847 |
Copiers | 4.57244665749 |
Air compressors | 0.0 |
Small kitchens / coffee rooms | 5.83121432556 |
Large kitchens | 0.0 |
Elevators | 0.537934900882 |
Laundry | 0.0 |
Electric engine heaters | 0.0 |
Circulation fans | 0.0 |
Miscellaneous | 13.7223350823 |
Total | 100.0 |
References | Swedish Energy Agency[2] |