Sweden Building 05K0118
Start Page
General Information
Year of construction | 1968 |
---|---|
Category | Office |
Boundaries | One building |
Ownership Category | County council |
Total floor area (BRA), m2 | 9200.0 |
OID, m2 | 9500.0 |
Interior height, m | 3.0 |
Year of construction 1 (taxation year) | 1968 |
Year of construction 2 (Year of construction) | 1968 |
County | Västernorrland County, Sweden |
Mean annual temperature during the calculation period[1] | 4.98333333333 |
Mean annual temperature at the site | 3.8 |
Start of the period (first day of the month) | 2004/01/01 |
End of the period (last day of the month) | 2004/12/01 |
References | Swedish Energy Agency[2] |
Areas by category, m2 (Gross Floor Area)
- Offices | 9200.0
|
---|---|
Total | 9200.0 |
References | Swedish Energy Agency[2] |
Purchased energy for the period [MWh/year]
Electricity, total | 1130.96 |
---|---|
District heating | 1384.0 |
Oil-fired boiler | 0.0 |
Natural gas | 0.0 |
Town gas | 0.0 |
Digester / landfill gas | 0.0 |
Pellets | 0.0 |
Wood chips | 0.0 |
Logs | 0.0 |
District cooling | 0.0 |
Other | 0.0 |
Total | 2514.96 |
References | Swedish Energy Agency[2] |
Purchased energy, normal year [MWh/year]
Electricity, total | 1130.96 |
---|---|
District heating | 1508.0 |
Oil-fired boiler | 0.0 |
Natural gas | 0.0 |
Town gas | 0.0 |
Digester / landfill gas | 0.0 |
Pellets | 0.0 |
Wood chips | 0.0 |
Logs | 0.0 |
District cooling | 0.0 |
Other | 0.0 |
Total | 2638.96 |
References | Swedish Energy Agency[2] |
Purchased energy per area [kWh/m2]
Electricity, total | 122.930434783 |
---|---|
Electric heating | 0.0 |
Other electricity | 122.930434783 |
District heating | 163.913043478 |
Oil-fired boiler | 0.0 |
Natural gas | 0.0 |
Town gas | 0.0 |
Digester / landfill gas | 0.0 |
Pellets | 0.0 |
Wood chips | 0.0 |
Logs | 0.0 |
District cooling | 0.0 |
Other | 0.0 |
Total | 286.843478261 |
Breakdown of electricity use [kWh/m2]
Electric heating | 0.0 |
---|---|
Heat pumps | 0.0 |
Refrigeration | 9.24927536232 |
Heat pumps used for cooling | 0.952173913043 |
Pumps | 3.55789236025 |
Fans | 35.3392546584 |
Lighting | 17.3777173913 |
PCs | 3.29956521739 |
Large computers / servers | 30.4695652174 |
Printers | 0.70652173913 |
Copiers | 1.03804347826 |
Air compressors | 0.880434782609 |
Small kitchens / coffee rooms | 1.37934782609 |
Large kitchens | 0.0 |
Elevators | 0.407608695652 |
Laundry | 0.0 |
Electric engine heaters | 2.6902173913 |
Circulation fans | 0.0 |
Miscellaneous | 20.1056428364 |
Total | 127.45326087 |
References | Swedish Energy Agency[2] |
Breakdown of electricity use [%]
Electric heating | 0.0 |
---|---|
Heat pumps | 0.0 |
Refrigeration | 7.2569938966 |
Heat pumps used for cooling | 0.747076933573 |
Pumps | 2.79152713393 |
Fans | 27.7272267632 |
Lighting | 13.6345804515 |
PCs | 2.58884330999 |
Large computers / servers | 23.9064618743 |
Printers | 0.554337907332 |
Copiers | 0.814450310003 |
Air compressors | 0.69079031529 |
Small kitchens / coffee rooms | 1.08223816062 |
Large kitchens | 0.0 |
Elevators | 0.319810331153 |
Laundry | 0.0 |
Electric engine heaters | 2.11074818561 |
Circulation fans | 0.0 |
Miscellaneous | 15.7749144269 |
Total | 100.0 |
References | Swedish Energy Agency[2] |