Sweden Building 05K0003
Start Page
General Information
Year of construction | 1960 |
---|---|
Category | Office |
Boundaries | One building |
Ownership Category | Private company |
Total floor area (BRA), m2 | 4855.0 |
OID, m2 | 4920.0 |
Interior height, m | 3.0 |
Year of construction 1 (taxation year) | 0Unable to interpret the "0" input value as valid date or time component with "There is no year 0 in Gregorian and Julian calendars." being reported. |
Year of construction 2 (Year of construction) | 1960 |
County | Stockholm County, Sweden |
Mean annual temperature during the calculation period[1] | 7.14166666667 |
Mean annual temperature at the site | 6.6 |
Start of the period (first day of the month) | 2004/01/01 |
End of the period (last day of the month) | 2004/12/01 |
References | Swedish Energy Agency[2] |
Areas by category, m2 (Gross Floor Area)
- Offices | 4360.0 |
---|---|
- Warehouses | 94.0
|
Total | 4454.0 |
References | Swedish Energy Agency[2] |
Purchased energy for the period [MWh/year]
Electricity, total | 321.8 |
---|---|
District heating | 473.4 |
Oil-fired boiler | 0.0 |
Natural gas | 0.0 |
Town gas | 0.0 |
Digester / landfill gas | 0.0 |
Pellets | 0.0 |
Wood chips | 0.0 |
Logs | 0.0 |
District cooling | 51.9 |
Other | 0.0 |
Total | 847.1 |
References | Swedish Energy Agency[2] |
Purchased energy, normal year [MWh/year]
Electricity, total | 321.8 |
---|---|
District heating | 498.4 |
Oil-fired boiler | 0.0 |
Natural gas | 0.0 |
Town gas | 0.0 |
Digester / landfill gas | 0.0 |
Pellets | 0.0 |
Wood chips | 0.0 |
Logs | 0.0 |
District cooling | 51.9 |
Other | 0.0 |
Total | 872.1 |
References | Swedish Energy Agency[2] |
Purchased energy per area [kWh/m2]
Electricity, total | 72.2496632241 |
---|---|
Electric heating | 0.0 |
Other electricity | 72.2496632241 |
District heating | 111.899416255 |
Oil-fired boiler | 0.0 |
Natural gas | 0.0 |
Town gas | 0.0 |
Digester / landfill gas | 0.0 |
Pellets | 0.0 |
Wood chips | 0.0 |
Logs | 0.0 |
District cooling | 11.6524472384 |
Other | 0.0 |
Total | 195.801526718 |
Breakdown of electricity use [kWh/m2]
Electric heating | 0.0 |
---|---|
Heat pumps | 0.0 |
Refrigeration | 0.0 |
Heat pumps used for cooling | 0.0 |
Pumps | 3.38991548528 |
Fans | 20.3514016294 |
Lighting | 25.3519773429 |
PCs | 4.12075688073 |
Large computers / servers | 0.0 |
Printers | 0.412844036697 |
Copiers | 0.447247706422 |
Air compressors | 0.0 |
Small kitchens / coffee rooms | 1.46100917431 |
Large kitchens | 0.0 |
Elevators | 5.78356533453 |
Laundry | 0.0 |
Electric engine heaters | 0.0 |
Circulation fans | 2.80646609789 |
Miscellaneous | 8.78442379242 |
Total | 72.9096074806 |
References | Swedish Energy Agency[2] |
Breakdown of electricity use [%]
Electric heating | 0.0 |
---|---|
Heat pumps | 0.0 |
Refrigeration | 0.0 |
Heat pumps used for cooling | 0.0 |
Pumps | 4.64947707499 |
Fans | 27.9131959869 |
Lighting | 34.7717923865 |
PCs | 5.65187088935 |
Large computers / servers | 0.0 |
Printers | 0.566240926214 |
Copiers | 0.613427670065 |
Air compressors | 0.0 |
Small kitchens / coffee rooms | 2.00386372221 |
Large kitchens | 0.0 |
Elevators | 7.93251470469 |
Laundry | 0.0 |
Electric engine heaters | 0.0 |
Circulation fans | 3.84924044288 |
Miscellaneous | 12.0483761962 |
Total | 100.0 |