General Information

Year of construction 1987
Category Office
Boundaries One building
Ownership Category Private company
Total floor area (BRA), m2 19400.0
OID, m2 19990.0
Interior height, m 3.0
Year of construction 1 (taxation year) 1987
Year of construction 2 (Year of construction) 1987
County Västernorrland County, Sweden
Mean annual temperature during the calculation period[1] 4.13333333333
Mean annual temperature at the site 3.6
Start of the period (first day of the month) 2004/10/01
End of the period (last day of the month) 2005/09/01
References Swedish Energy Agency[2]

Areas by category, m2 (Gross Floor Area)

- Offices 19000.0













- Miscellaneous 400.0
Total 19400.0
References Swedish Energy Agency[2]

Purchased energy for the period [MWh/year]

Electricity, total 2078.0
District heating 788.0
Oil-fired boiler 0.0
Natural gas 0.0
Town gas 0.0
Digester / landfill gas 0.0
Pellets 0.0
Wood chips 0.0
Logs 0.0
District cooling 0.0
Other 0.0
Total 2866.0
References Swedish Energy Agency[2]

Purchased energy, normal year [MWh/year]

Electricity, total 2079.02242152
District heating 820.887892377
Oil-fired boiler 0.0
Natural gas 0.0
Town gas 0.0
Digester / landfill gas 0.0
Pellets 0.0
Wood chips 0.0
Logs 0.0
District cooling 0.0
Other 0.0
Total 2899.9103139
References Swedish Energy Agency[2]

Purchased energy per area [kWh/m2]

Electricity, total 107.166104202
Electric heating 1.2
Other electricity 105.966104202
District heating 42.3138088854
Oil-fired boiler 0.0
Natural gas 0.0
Town gas 0.0
Digester / landfill gas 0.0
Pellets 0.0
Wood chips 0.0
Logs 0.0
District cooling 0.0
Other 0.0
Total 149.479913088

Breakdown of electricity use [kWh/m2]

Electric heating 1.2
Heat pumps 0.0
Refrigeration 12.0535714286
Heat pumps used for cooling 1.33928571429
Pumps 9.54215394737
Fans 24.4440225564
Lighting 18.56361338
PCs 5.02894736842
Large computers / servers 5.52631578947
Printers 0.898421052632
Copiers 1.05789473684
Air compressors 0.0
Small kitchens / coffee rooms 1.85684210526
Large kitchens 4.61052631579
Elevators 0.421052631579
Laundry 0.0428421052632
Electric engine heaters 2.52631578947
Circulation fans 0.0
Miscellaneous 22.590231015
Total 111.702035936
References Swedish Energy Agency[2]

Breakdown of electricity use [%]

Electric heating 1.07428659643
Heat pumps 0.0
Refrigeration 10.7908251873
Heat pumps used for cooling 1.19898057637
Pumps 8.54250673891
Fans 21.8832381626
Lighting 16.6188675295
PCs 4.50210896002
Large computers / servers 4.94737248354
Printers 0.804301412324
Copiers 0.947068446849
Air compressors 0.0
Small kitchens / coffee rooms 1.66231715447
Large kitchens 4.12752218627
Elevators 0.376942665413
Laundry 0.0383539162057
Electric engine heaters 2.26165599248
Circulation fans 0.0
Miscellaneous 20.2236519914
Total 100.0
References Swedish Energy Agency[2]

References

  1. Swedish Meteorological and Hydrological Institute