Sweden Building 05K0053

Jump to: navigation, search

Start Page

General Information

Year of construction 1990
Category Office
Boundaries One building
Ownership Category Private company
Total floor area (BRA), m2 6340.0
OID, m2 6500.0
Interior height, m 3.0
Year of construction 1 (taxation year) 1990
Year of construction 2 (Year of construction) 1990
County Stockholm County, Sweden
Mean annual temperature during the calculation period[1] 7.6
Mean annual temperature at the site 6.6
Start of the period (first day of the month) 2004/01/01
End of the period (last day of the month) 2004/12/01
References Swedish Energy Agency[2]

Areas by category, m2 (Gross Floor Area)

- Offices 6340.0














Total 6340.0
References Swedish Energy Agency[2]

Purchased energy for the period [MWh/year]

Electricity, total 541.0
District heating 547.0
Oil-fired boiler 0.0
Natural gas 0.0
Town gas 0.0
Digester / landfill gas 0.0
Pellets 0.0
Wood chips 0.0
Logs 0.0
District cooling 0.0
Other 0.0
Total 1088.0
References Swedish Energy Agency[2]

Purchased energy, normal year [MWh/year]

Electricity, total 541.0
District heating 580.0
Oil-fired boiler 0.0
Natural gas 0.0
Town gas 0.0
Digester / landfill gas 0.0
Pellets 0.0
Wood chips 0.0
Logs 0.0
District cooling 0.0
Other 0.0
Total 1121.0
References Swedish Energy Agency[2]

Purchased energy per area [kWh/m2]

Electricity, total 85.3312302839
Electric heating 0.0
Other electricity 85.3312302839
District heating 91.4826498423
Oil-fired boiler 0.0
Natural gas 0.0
Town gas 0.0
Digester / landfill gas 0.0
Pellets 0.0
Wood chips 0.0
Logs 0.0
District cooling 0.0
Other 0.0
Total 176.813880126

Breakdown of electricity use [kWh/m2]

Electric heating 0.0
Heat pumps 0.0
Refrigeration 4.29022082019
Heat pumps used for cooling 0.757097791798
Pumps 7.39287629563
Fans 34.9414713835
Lighting 22.106466877
PCs 2.54574132492
Large computers / servers 0.0
Printers 0.583596214511
Copiers 1.02523659306
Air compressors 0.0
Small kitchens / coffee rooms 2.24921135647
Large kitchens 0.0
Elevators 0.315457413249
Laundry 0.0
Electric engine heaters 2.36593059937
Circulation fans 0.0
Miscellaneous 9.88095200541
Total 88.4542586751
References Swedish Energy Agency[2]

Breakdown of electricity use [%]

Electric heating 0.0
Heat pumps 0.0
Refrigeration 4.85021398003
Heat pumps used for cooling 0.855920114123
Pumps 8.35785230283
Fans 39.5023053801
Lighting 24.9919757489
PCs 2.87803138374
Large computers / servers 0.0
Printers 0.659771754636
Copiers 1.15905848787
Air compressors 0.0
Small kitchens / coffee rooms 2.54279600571
Large kitchens 0.0
Elevators 0.356633380884
Laundry 0.0
Electric engine heaters 2.67475035663
Circulation fans 0.0
Miscellaneous 11.1706911045
Total 100.0
References Swedish Energy Agency[2]

References

  1. Swedish Meteorological and Hydrological Institute