Sweden Building 05K0008

Jump to: navigation, search

Start Page

General Information

Year of construction 1997
Category Office
Boundaries One building
Ownership Category Government building
Total floor area (BRA), m2 7800.0
OID, m2 8040.0
Interior height, m 3.0
Year of construction 1 (taxation year) 1997
Year of construction 2 (Year of construction) 1997
County Stockholm County, Sweden
Mean annual temperature during the calculation period[1] 7.73333333333
Mean annual temperature at the site 6.6
Start of the period (first day of the month) 2004/10/01
End of the period (last day of the month) 2005/09/01
References Swedish Energy Agency[2]

Areas by category, m2 (Gross Floor Area)

- Restaurants 300.0
- Offices 7500.0














Total 7800.0
References Swedish Energy Agency[2]

Purchased energy for the period [MWh/year]

Electricity, total 315.0
District heating 844.0
Oil-fired boiler 0.0
Natural gas 0.0
Town gas 0.0
Digester / landfill gas 0.0
Pellets 0.0
Wood chips 0.0
Logs 0.0
District cooling 123.0
Other 0.0
Total 1282.0
References Swedish Energy Agency[2]

Purchased energy, normal year [MWh/year]

Electricity, total 315.0
District heating 898.0
Oil-fired boiler 0.0
Natural gas 0.0
Town gas 0.0
Digester / landfill gas 0.0
Pellets 0.0
Wood chips 0.0
Logs 0.0
District cooling 123.0
Other 0.0
Total 1336.0
References Swedish Energy Agency[2]

Purchased energy per area [kWh/m2]

Electricity, total 40.3846153846
Electric heating 0.0
Other electricity 40.3846153846
District heating 115.128205128
Oil-fired boiler 0.0
Natural gas 0.0
Town gas 0.0
Digester / landfill gas 0.0
Pellets 0.0
Wood chips 0.0
Logs 0.0
District cooling 15.7692307692
Other 0.0
Total 171.282051282

Breakdown of electricity use [kWh/m2]

Electric heating 0.0
Heat pumps 0.0
Refrigeration 0.0
Heat pumps used for cooling 0.0
Pumps 3.32543498168
Fans 9.28527472527
Lighting 15.7053876478
PCs 4.66333333333
Large computers / servers 0.0
Printers 0.0
Copiers 0.9
Air compressors 0.0
Small kitchens / coffee rooms 0.910666666667
Large kitchens 0.0
Elevators 0.192307692308
Laundry 0.0
Electric engine heaters 0.0
Circulation fans 0.625641025641
Miscellaneous 6.03377747253
Total 41.6418235453
References Swedish Energy Agency[2]

Breakdown of electricity use [%]

Electric heating 0.0
Heat pumps 0.0
Refrigeration 0.0
Heat pumps used for cooling 0.0
Pumps 7.98580537202
Fans 22.2979541594
Lighting 37.7154176036
PCs 11.1986770422
Large computers / servers 0.0
Printers 0.0
Copiers 2.16128863574
Air compressors 0.0
Small kitchens / coffee rooms 2.18690390846
Large kitchens 0.0
Elevators 0.461813811056
Laundry 0.0
Electric engine heaters 0.0
Circulation fans 1.5024342653
Miscellaneous 14.4897052022
Total 100.0
References Swedish Energy Agency[2]

References

  1. Swedish Meteorological and Hydrological Institute
  2. Swedish Energy Agency