Eaton D64L Series Ground Fault Monitor

Manufacturer: Eaton
Measurement Category: Electric & Power, Condition Monitoring
Operating Environment: Dry Enclosed Space
Mounting: DIN Rail
Operating Mode: Free Streaming
Power Supply Type: VAC




Description

Type D64L ground fault monitors are designed to monitor ungrounded supplies on three-phase AC power systems up to 600 V. If an insulation fault develops anywhere on the system between the source and the load, the D64L will detect it and give an alarm or trip, depending on the adjustable field settings selected.


Sensor Measurements

  • Ground Fault (Electronic Health)

Measurement Specifications
Adjustable leakage current seting: 20 mA, 35 mA or 50 mA
Control power 110/120 V or 220/240 V at 50-60 Hz


Notes, Considerations & Recommendations