At Hooligans, the Aisin G60 is integrated into the facility’s existing domestic hot water and electrical distribution systems. The output of the cogeneration unit is 120/240v, 60 Hz single phase. The restaurant has an 800 amp 120/208v three phase service. Installation of the Aisin G60 required the addition of a 120/240 to 120v isolation transformer in order for the restaurant service to properly accept the unit output. The connection was made to the phase with the highest normal load, so as to bring the load into greater balance.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current14:31, 4 October 2012Thumbnail for version as of 14:31, 4 October 20121,275 × 1,650, 47 pages (386 KB)Bryonbean (Talk | contribs)At Hooligans, the Aisin G60 is integrated into the facility’s existing domestic hot water and electrical distribution systems. The output of the cogeneration unit is 120/240v, 60 Hz single phase. The restaurant has an 800 amp 120/208v three phase servic