Distributed Generation Study/Arrow Linen

Jump to: navigation, search
Study Location Brooklyn, New York
Site Description Commercial-Other
Study Type Long-term Monitoring
Technology Internal Combustion Engine
Prime Mover Coast Intelligen 150-IC with ECS
Heat Recovery Systems Built-in
Fuel Natural Gas
System Installer Energy Concepts
System Enclosure Outdoor
System Application Combined Heat and Power
Number of Prime Movers 2
Stand-alone Capability None
Power Rating 300 kW0.3 MW
300,000 W
300,000,000 mW
3.0e-4 GW
3.0e-7 TW
Nominal Voltage (V) 480
Heat Recovery Rating (BTU/hr) 3000000
Cooling Capacity (Refrig/Tons)
Origin of Controller 3rd Party Off-the-Shelf
Component Integration Customer Assembled
Start Date 2005/03/01
Monitoring Termination Date 1969/12/31
Primary Power Application Based Load
Secondary Power Application
Primary Heat/Cooling Application Domestic Hot Water
Secondary Heat/Cooling Application Domestic Hot Water
Capacity Factor .345
Availability 99.12
Electrical Efficiency (HHV)
Electrical Efficiency (LHV)
Highest Combustion Intake Air Temperature (F) 121.3°F322.761 K
49.611 °C
580.97 °R
Lowest Combustion Intake Air Temperature (F) 11°F261.483 K
-11.667 °C
470.67 °R
NOx Emissions Data Available No
CO Emissions Data Available No
12-Month Run Hours 22171
12-Month Energy Savings (USD)
System Cost (USD)
Report URL http://chp.nyserda.org/facilities/details.cfm?facility=31
Study Verified Yes